CVE-2024-1573

CVSS V2 None CVSS V3 None
Description
Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting. * “Automatic log in” option is enabled in the security setting. * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account. * The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in.
Overview
  • CVE ID
  • CVE-2024-1573
  • Assigner
  • Mitsubishi
  • Vulnerability Status
  • PUBLISHED
  • Published Version
  • 2024-07-04T08:59:44.079Z
  • Last Modified Date
  • 2024-07-04T08:59:44.079Z
History
Created Old Value New Value Data Type Notes
2024-07-05 13:03:54 Added to TrackCVE