CVE-2023-39464

CVSS V2 None CVSS V3 None
Description
Triangle MicroWorks SCADA Data Gateway GTWWebMonitorService Unquoted Search Path Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the configuration of the GTWWebMonitorService service. The path to the service executable contains spaces not surrounded by quotations. An attacker can leverage this vulnerability to execute arbitrary code in the context of root. Was ZDI-CAN-20538.
Overview
  • CVE ID
  • CVE-2023-39464
  • Assigner
  • zdi
  • Vulnerability Status
  • PUBLISHED
  • Published Version
  • 2024-05-03T01:59:27.382Z
  • Last Modified Date
  • 2024-06-04T17:27:11.296Z
History
Created Old Value New Value Data Type Notes
2024-06-25 19:06:42 Added to TrackCVE