CVE-2022-41629

CVSS V2 None CVSS V3 Critical 9.1
Description
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the “RunningConfigs” directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords.
Overview
  • CVE ID
  • CVE-2022-41629
  • Assigner
  • ics-cert@hq.dhs.gov
  • Vulnerability Status
  • Analyzed
  • Published Version
  • 2022-10-31T20:15:13
  • Last Modified Date
  • 2022-11-02T12:59:49
CPE Configuration (Product)
CPE Vulnerable Operator Version Start Version End
cpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:* 1 OR 00.00.02a
CVSS Version 3
  • Version
  • 3.1
  • Vector String
  • CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
  • Attack Vector
  • NETWORK
  • Attack Compatibility
  • LOW
  • Privileges Required
  • NONE
  • User Interaction
  • NONE
  • Scope
  • UNCHANGED
  • Confidentiality Impact
  • HIGH
  • Availability Impact
  • NONE
  • Base Score
  • 9.1
  • Base Severity
  • CRITICAL
  • Exploitability Score
  • 3.9
  • Impact Score
  • 5.2
References
History
Created Old Value New Value Data Type Notes
2022-10-31 21:00:06 Added to TrackCVE
2022-12-07 15:11:04 2022-10-31T20:15Z 2022-10-31T20:15:13 CVE Published Date updated
2022-12-07 15:11:04 2022-11-02T12:59:49 CVE Modified Date updated
2022-12-07 15:11:04 Analyzed Vulnerability Status updated