CVE-2020-24685

CVSS V2 Medium 5 CVSS V3 High 8.6
Description
An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions.
Overview
  • CVE ID
  • CVE-2020-24685
  • Assigner
  • cybersecurity@ch.abb.com
  • Vulnerability Status
  • Analyzed
  • Published Version
  • 2021-02-09T04:15:14
  • Last Modified Date
  • 2021-02-16T16:09:53
CPE Configuration (Product)
CPE Vulnerable Operator Version Start Version End
AND
cpe:2.3:o:abb:ac500_cpu_firmware:*:*:*:*:*:*:*:* 1 OR 2.8.5
cpe:2.3:h:abb:pm573-eth:2.0:*:*:*:*:*:*:* 0 OR
cpe:2.3:h:abb:pm583-eth:2.0:*:*:*:*:*:*:* 0 OR
CVSS Version 2
  • Version
  • 2.0
  • Vector String
  • AV:N/AC:L/Au:N/C:N/I:N/A:P
  • Access Vector
  • NETWORK
  • Access Compatibility
  • LOW
  • Authentication
  • NONE
  • Confidentiality Impact
  • NONE
  • Integrity Impact
  • NONE
  • Availability Impact
  • PARTIAL
  • Base Score
  • 5
  • Severity
  • MEDIUM
  • Exploitability Score
  • 10
  • Impact Score
  • 2.9
CVSS Version 3
  • Version
  • 3.1
  • Vector String
  • CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
  • Attack Vector
  • NETWORK
  • Attack Compatibility
  • LOW
  • Privileges Required
  • NONE
  • User Interaction
  • NONE
  • Scope
  • CHANGED
  • Confidentiality Impact
  • NONE
  • Availability Impact
  • HIGH
  • Base Score
  • 8.6
  • Base Severity
  • HIGH
  • Exploitability Score
  • 3.9
  • Impact Score
  • 4
History
Created Old Value New Value Data Type Notes
2022-05-10 07:23:16 Added to TrackCVE
2022-12-05 21:37:37 2021-02-09T04:15Z 2021-02-09T04:15:14 CVE Published Date updated
2022-12-05 21:37:37 2021-02-16T16:09:53 CVE Modified Date updated
2022-12-05 21:37:37 Analyzed Vulnerability Status updated